Dimensions
|
:
|
8.20" (209 mm) W x 9.30" (237 mm) L x 2.00" (51 mm) H
|
Number of Devices Supported
|
:
|
Modbus: 32 device on one network, Analog: 4, Pulse: 4
|
Supply Power
|
:
|
24 VDC or 120 - 240 VAC
|
The H8822 AcquiSuite data acquisition system is the perfect do-it yourself solution for your energy logging needs. This server combines the flexibility of Ethernet LAN, WAN, or internet communication paths with a low installed cost. It is an ideal device for recording electrical, natural gas, water and other building energy usages. After installation, data from a connected device is time-stamped and stored in nonvolatile memory at user-selected intervals until the next scheduled upload to the SQL database server. Using the built-in phone modem, Ethernet port or cellular modem, the AcquiSuite sends data to the Building Manager Online server or to other third party software providers.
- Plug and play - install and configure in minutes
- Flexible data formats - hardware and software provide data in flexible, industry standard formats for databases, spreadsheets, etc
- LCD display - easy installation and troubleshooting
- Integrated web server - provides setup and configuration using any standard web browser
- 8x pulse input, 4 modem activity, Modbus TX/RX, power status LEDs
- 2 x 16 LCD character, two buttons LCD
- User selectable 1 to 60 min, default 15 min interval recording
- 8x, user selectable - 0 to 10 V: min/max/ave/instantaneous; 4 to 20 mA: min/max/ave/instantaneous; pulse: consumption, rate; resistance: min/max/ave/instantaneous; runtime: runtime, status inputs
- 2x, dry contact 30 VDC, 150 mA maximum outputs
- 10/100, auto-crossover detection LAN
-
CE Declaration
https://staging.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/h82-CEDec10071.pdf
-
Datasheet
https://staging.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/H8822_d0117.pdf
-
Installation Guide
https://staging.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/h8822_i0c2.pdf