Important Announcement: Pricing Changes in 2023 Read More
Plant will be closed from December 26th-January 3rd. Read More
  • We can help. Call 800-354-8556

Veris GWNPXX Gas Sensor Base

Protocol (BACnet/Modbus) Output Modular Gas Sensor Platform

  • Brand Name: Veris
  • Veris Part#: GWNPXX
  • Est. Shipping Date: loading
Measurement Type      :      None
Outputs      :      Protocol Communication
Communication      :      BACnet (MS/TP) | Modbus (RTU)
Application      :      Parking Garage | Space Gas Detection
Application Zone      :      Parking Garage | Plant Room | Living Space
Brand      :      Veris
Color      :      Black
Communication Specifications      :      Baud Rate: 9600, 19200, 38400, 57600 (ModBus), 76800 (BACnet)
Dimension Depth      :      Installed Depth: 1.2" (30 mm), total depth: 2.3" (57 mm)
Dimension Height      :      4.5" (113 mm)
Dimension Width      :      2.75" (70 mm)
Electrical Wiring Size      :      24 - 12 AWG (0.22 - 2.5 mm²)
Enclosure Material      :      ABS Plastic
IP Protection      :      IP20
Model      :      GWN
Mounting      :      North American Duplex Box
Operating Humidity      :      0 - 90% RH, non-condensing
Operating Temperature      :      -4 - 122 °F (-20 - 50 °C)
Product Type      :      Sensor Base
Range      :      GWNP
Product Certification      :      CE | ETL
Warranty      :      5 years
LED Indicator Type      :      Green: On/Yellow: Low Setpoint/Red: High Setpoint
Operating Current      :      60 mA max.
Standards EMC      :      UL 61010-1
Supply Voltage AC Nominal      :      24 VAC
Supply Voltage AC Range      :      20 - 28 VAC
Supply Voltage DC Nominal      :      24 VDC
Supply Voltage DC Range      :      15 - 30 VDC

GWNP series protocol communications platform offers a convenient means for sensing gases in the environment. The GWNP is mounted to any single-gang electrical box and wired to the building controller. Then, a single AGxx gas sensor (sold separately) is installed in the GWNP. With this design, there is no need for a costly new installation when a sensor reaches the end of its life. The GWNP platform remains installed, and the installer simply opens the GWNP housing to replace the modular sensor inside, reducing labor costs and downtime. AG series sensors can be swapped in the GWNP platform at any time with minimal effort. The GWNP platform converts the signal from the AG sensor into protocol communications compatible with building control systems.

  • Communication - interface to control system via BACnet and Modbus protocols. BTL certified
  • Modular platform accepts Veris AG series sensors (sold separately) no need to install a new GWNP when the sensor life wears out
  • Three colored LEDs - red, yellow and green - for easy status viewing
  • Microprocessor controlled excellent stability operation
  • No calibration required, easy maintenance and worry-free
  • Versatile interface - interface to DDC systems or direct fan control
  • pdf Datasheet https://staging.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/GWNP_d0117.pdf
  • pdf Installation Guide https://staging.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/gwnp_i0c2.pdf