Veris TIWA0D0 Pipe/Immersion Temperature Sensor

Stainless Steel Probe 2-1/2 in 10 kOhm T2 Thermistor NTC Immersion Temperature Sensor, Water Resistant Housing Enclosure

  • Brand Name: Veris
  • Veris Part#: TIWA0D0
  • Est. Shipping Date: loading
Mounting      :      Pipe with Water Resistant Housing
Temperature Sensor Type      :      10k Ohm Type 2 Thermistor
Temperature Calibration Certificate      :      None
Outputs      :      Resistive output
Application      :      Pipe | Immersion
Application Zone      :      Plant Room
Brand      :      Veris
Dimension Depth      :      2" (51 mm)
Dimension Height      :      4.6" (117 mm)
Dimension Probe Diameter      :      0.25" (6 mm) with 1/2" NPT thread at base
Thermowell      :      Not Included
Dimension Width      :      2.9" (74 mm)
Electrical Wiring Size      :      22 AWG (0.32 mm²)
Enclosure Material      :      Aluminum Box, Stainless Steel Cover
Measurement Type      :      Temperature
Model      :      TIWA0D0
Operating Temperature      :      -13 - 221 °F (-25 - 105 °C)
Product Type      :      Sensor
Range      :      TI
Temperature Measurement Accuracy      :      ±1.8 °F (±1.0 °C)
Temperature Measurement Range      :      -58 - 302 °F (-50 - 150 °C)
Warranty      :      5 years

These immersion probe type temperature sensors are both highly accurate and cost effective. Installation could not be easier. The sensor is encased in a corrosion-resistant stainless steel probe for durability, with a choice of service entry body, indoor junction box, or threaded enclosures. A variety of RTD or thermistor sensor options and probe lengths are available for maximum application versatility.

  • Durable - corrosion resistant stainless steel probe design
  • Easy selection - 1/2 in NPT threads standard
  • Cost-effective, high accuracy thermistors/RTDs
  • Water resistant housing enclosure
  • pdf Datasheet https://staging.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/tida0b0_dat.pdf
  • pdf Installation Guide https://staging.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/tida0b0_ig.pdf