| Application | : | Resistive to Analog Converter |
| Temperature Measurement Range | : | 0 - 151 °F (-18 - 66 °C) |
| Application Zone | : | Plant Room |
| Brand | : | Veris |
| Dimension Depth | : | 1.5" (39 mm) |
| Dimension Height | : | 1.5" (39 mm) |
| Dimension Width | : | 1.5" (39 mm) |
| Input Specifications | : | 100 Ohm Platinum RTD |
| Inputs | : | Resistive input |
| Model | : | AA10B-18C66 |
| Output Specifications | : | 4 - 20 mA |
| Outputs | : | Analog output |
| Product Type | : | Accessory |
| Supply Voltage DC Range | : | 9 - 30 VDC |
| Temperature Measurement Accuracy | : | ±1.5 °F (±0.8 °C) |
| Electrical Wiring | : | 2-wires (loop-powered) |
| Enclosure Material | : | Epoxy encapsulated |
| Operating Temperature | : | 5 - 122 °F (-15 - 50 °C) |
| Product Certification | : | CE |
| Warranty | : | 5 years |
| Standards | : | RoHS |
The AA10 series temperature-to-current transmitter is designed for use with 100 Ohm platinum RTD 3 external resistive output devices. When the resistive output from the external device is connected to the AA10 input terminal, the resistive value is converted to a 4 to 20 mA signal compatible with most building control systems.