Veris PW2XN05S Wet Differential Pressure Sensor

12 to 24 VDC Input 4 to 20 mA Output Wet Media Differential Pressure Transducer, 0 to 250 psig, NIST

  • Brand Name: Veris
  • Veris Part#: PW2XN05S
  • Est. Shipping Date: loading
Display Type      :      None
Mounting      :      Panel
Pressure Measurement Range      :      0 - 25 psi (0 - 1.7 bar) | 0 - 50 psi (0 - 3.5 bar) | 0 - 100 psi (0 - 7 bar) | 0 - 250 psi (0 - 17 bar)
Output Specifications      :      4 - 20 mA
Application      :      Pump and Compressor Differential Pressure | Chiller Differential Pressure Monitoring
Application Zone      :      Plant Room
Burst Pressure      :      1,250 psi (85 bar)
Calibration Certificate      :      NIST Certificate
Dimension Depth      :      2.2" (56 mm)
Dimension Height      :      4" (102 mm)
Dimension Width      :      5.8" (147 mm)
Electrical Wiring      :      2-wires (loop-powered)
Enclosure Material      :      Powder Coated Aluminium
Fitting Material      :      Stainless Steel
Fitting Size      :      1/ 8” NPT
Fitting Type      :      Female
IP Protection      :      IP65 (NEMA 4)
Measurement Type      :      Differential Pressure
Model      :      PW2XN05S
Outputs      :      Analog output
Product Type      :      Sensor
Range      :      PW2
Brand      :      Veris
Medium      :      Water
Product Certification      :      CE
Pressure Measurement Accuracy      :      Range A, B and C: ±1% of F.S. Range D: ±2% of F.S.
Supply Voltage DC Range      :      12 - 24 VDC
Operating Current      :      29 mA
Operating Humidity      :      0 - 90% RH, non-condensing
Operating Temperature      :      14 - 130 °F (-10 - 55 °C)
Standards EMC      :      EN 61000-6-1
Warranty      :      5 years

The PW2 series 2-wire, 4 to 20 mA wet pressure transducers incorporate microprocessor profiled sensors for exceptional accuracy and reliability. Easy to use and designed to provide exceptional installation savings, the PW2 series is ideal for measuring pressure across pumps, filters, heat exchangers, compressors and other non-corrosive wet media applications.

  • The jumper-selectable output switch for normal (4 to 20 mA) or reverse (20 to 4 mA) operation provides application flexibility
  • Rugged, die-cast enclosure provides NEMA 4 sealing
  • Selectable differential units: psid or bard
  • Dual sensor design for improved overpressure tolerance, eliminates the requirement for a bypass valve assembly in most applications
  • Jumper-controlled electronic surge dampening for high stability
  • Pushbutton zero calibration - no trim pots to adjust, maintain accuracy and reduce callbacks with automatic zero calibration
  • 2-wire transmitter output
  • User-selectable output
  • NIST certified
  • 2 times of maximum full scale range proof pressure
  • 5 times of maximum full scale range burst pressure
 

Optional Accessories: AA14A, AA11, AA12, AA13

  • pdf CE Declaration https://staging.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/pw2-CEDec02081.pdf
  • pdf Datasheet https://staging.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/PW2_d1018.pdf
  • pdf Installation Guide https://staging.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/pw2_i0h2.pdf