Display Type | : | None |
Mounting | : | Panel |
Pressure Measurement Range | : | 0 - 10 psi (0 - 0.7 bar) | 0 - 20 psi (0 - 1.4 bar) | 0 - 50 psi (0 - 3.5 bar) | 0 - 100 psi (0 - 7 bar) |
Output Specifications | : | 4 - 20 mA | 0 - 5 V | 0 - 10 V |
Application | : | Pump and Compressor Differential Pressure | Chiller Differential Pressure Monitoring |
Application Zone | : | Plant Room |
Burst Pressure | : | 500 psi (34 bar) |
Calibration Certificate | : | No |
Dimension Depth | : | 2.2" (56 mm) |
Dimension Height | : | 4" (102 mm) |
Dimension Width | : | 5.8" (147 mm) |
Electrical Wiring | : | 3-wires |
Enclosure Material | : | Powder Coated Aluminium |
Fitting Material | : | Stainless Steel |
Fitting Size | : | 1/ 8” NPT |
Fitting Type | : | Female |
IP Protection | : | IP65 (NEMA 4) |
Measurement Type | : | Differential Pressure |
Model | : | PWXX04S |
Outputs | : | Analog output |
Product Type | : | Sensor |
Range | : | PW |
Brand | : | Veris |
Medium | : | Water |
Product Certification | : | CE |
Pressure Measurement Accuracy | : | Range A and B: ±1% of F.S. Range C: ±1.5% of F.S. Range D: ±2% of F.S. |
Supply Voltage AC Nominal | : | 24 VAC |
Supply Voltage DC Range | : | 15 - 30 VDC |
LED Indicator Type | : | Red and Green |
Operating Current | : | 125 - 280 mA |
Operating Humidity | : | 0 - 90% RH, non-condensing |
Operating Temperature | : | 14 - 122 °F (-10 - 50 °C) |
Standards EMC | : | EN 61000-6-1 |
Warranty | : | 5 years |
The PW series wet pressure transducers incorporate microprocessor profiled sensors for exceptional accuracy and reliability. Easy to use and designed to provide exceptional installation savings, the PW Series is ideal for measuring pressure across pumps, filters, heat exchangers, compressors and other non-corrosive wet media applications. The jumper-selectable port swap feature eliminates costly replumbing when the high and low ports are improperly plumbed, allowing the jumper position to be changed from normal to swap.
Optional Accessories: AA14A, AA11, AA12, AA13