Veris HT2NAS0H Humidistats

ABS Plastic +/-2% NIST 10 kOhm T3 Thermistor Humidistat and Thermostat Control, Analog Setpoint

  • Brand Name: Veris
  • Veris Part#: HT2NAS0H
  • Est. Shipping Date: loading
Measurement Type      :      Temperature | Humidity
Outputs      :      Analog output | Resistive temperature output
Output Specifications      :      4 - 20 mA | 0 - 5 V | 0 - 10 V
Temperature Sensor Type      :      10k Ohm Type 3 Thermistor
Humidity Calibration Certificate      :      NIST
Temperature Calibration Certificate      :      None
Application Zone      :      Living Space
Color      :      Cloud White
Display Size      :      1.2" x 0.6" (30.5 mm x 14 mm)
Display Type      :      LCD
Humidity Measurement Accuracy      :      ±2%
Model      :      HT2NAS0H
Mounting      :      Wall
Override      :      No
Product Type      :      Humidistat | Thermostat
Range      :      HWS
Product Certification      :      CE
Setpoint      :      Yes
Humidity Setpoint Range      :      0 - 100% RH
Temperature Setpoint Range      :      50 - 95 °F (10 - 35 °C) | 32 - 122 °F (0 - 50 °C)
Temperature Measurement Accuracy      :      ±0.4 °F (±0.2 °C)
Temperature Measurement Range      :      32 - 158 °F (0 - 70 °C)
Temperature Measurement Resolution      :      0.1 °
Warranty      :      5 years (1 year on replaceable RH element)

All HT series institutional grade relative humidity transmitters are designed to meet the rigorous needs of pharmaceutical labs, hospitals, science labs and other settings that call for precise environmental control. Internal jumpers control access to a feature that allows adjustment of the calibration offsets. The devices can also be made tamper resistant using a jumper to disable keypad programing functions. HT models are calibrated with NIST traceable calibration equipment. Analog output models feature a keypad to make adjusting humidity and temperature setpoint values easy. They transmit the setpoint values back to a control system by means of dual outputs. A slide-switch allows easy selection of output type, either 4 to 20 mA or 0 to 5 V/0 to 10 VDC signals. Dual outputs enable effortless control of both humidity and temperature in a single, compact sensor.

  • Analog setpoint outputs (TWS analog) provide application flexibility
  • LCD for local display of readings and setup values
  • Offset function adjusts calibration intervals for both RH and T
  • Switch-selectable 4 to 20 mA or 0 to 5/0 to 10 VDC analog outputs
  • Multi-point calibration to 1% RH, traceable to NIST
  • Saves time - replaceable RH sensor element supports field calibration offset
  • 2% NIST
  • Analog setpoint
  • Digitally profiled thin-film capacitive (32-bit mathematics) US Patent 5,844,138 RH sensor
  • pdf CE Declaration https://staging.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/hta-CEDec02081.pdf
  • pdf Datasheet https://staging.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/HT_HWS_d0117.pdf
  • pdf Installation Guide https://staging.veris.com//ASSETS/DOCUMENTS/ITEMS/EN/ht-analog_i0r2.pdf